LW64
The Pulsatron Series CW pump was designed to control conductivity and feed inhibitor in an open-air cooling tower. Chemical feed is initiated and controlled by input from a water meter. The Series CW combines everything you need to control conductivity and feed inhibit into one unique, compact package to create a simple and cost effective metering control system. The Series CW includes a solenoid actuated metering pump, conductivity sensor, bleed relay and a dry contact input for water meter control. At set-up, the operator sets the conductivity set point, differential (or dead-band), the pump stroke frequency and run time. When conductivity reaches the set point, the system activates the bleed relay. As make-up water passes through the water meter, it generates a series of pulses based on volume of flow. The pump counts the pulses until the total reaches the Count set point. The pump runs at the frequency and run-time specified at set-up and the count is reset.
Features: - 120 VAC or 250 VAC @50/60 Hz, 5A max
- 4-electrode conductivity input
- 0-6000 µS/cm ±1% temperature compensated
- Relay rated at 5A at 240 VAC
- Isolated dry contact flow switch input
- Isolated dry contact water meter input
- 4 Digit LED, 9 key membrane keypad
- Single-button function keys
- Set, Differential, Calibration, Pulse Timer, and Count functions
- Stroke rate adjusts 0-100% in 1% increments, turndown ratio 100:1.
Dimensions (inches): 5.0(A) x 9.9(B) x 9.5(C) x 6.5(D) x 8.5(E) See Below
Pulsatron Plus Series CW Metering Pump Datasheet Pulsatron Plus Series CW Metering Pump Owner's Manual Chemical Resistance Guide Pulsatron Pump Parts
|
|
|
|