CBL121X003
When Ordering Cabling The CE Agency Approval cable is required when working with an item with CE agency approval options. For applications requiring more than the standard 3 feet of cable, please contact us. Be prepared to provide the desired model number.
The following is the maximum cable length allowed per application. Level Wands .......................................................... 500ft / 152.5m Level Wands - multiple wands (4) in one cable ..... 500ft / 152.5m Flow Switch ........................................................... 500ft / 152.5m Series 9000 Conductivity Sensor ........................... 200ft / 61m DCS900 Conductivity Sensor ................................... 35ft / 10.5m 4-20mA Signals ...................................................... 500ft / 152.5m Dry Contact Water Meters ..................................... 500ft / 152.5m Hall Effect (paddle wheel) water meters ............... 500ft / 152.5m pH/ORP* .............................................................. 1000ft / 305m *for distances greater than 30 ft/9.2m, you must use a preamp.
|